Parameters
4.2 Motor control
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
101
Safety guidelines
Note
At least one additional digital module is required for this control function.
Note
Two current settings must be set for the pole
-changing starter:
I
s
1 for the SLOW speed
I
s
2 for the FAST speed.
Depending on the current range, the current can in many cases be directly measured at both
speeds with a single current transformer. Otherwise you will need two external current
transformers appropriate for the relevant s
peed (e.g. 3UF18 with a 1 A secondary
transformer rated current), whose secondary cables must lead through the current
measuring module within the range 0.3
to 3 A. The current setting I
s
1 or I
s
2 must be
converted according to the secondary currents of the
external transformers. For more
information, see Chapter
Overload protection (Page 34).

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals