Parameters   
4.8 Logic modules 
  SIMOCODE pro - Parameterize 
234  Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
 
Truth table for 3I / 1O 
Description 
The truth table for 3I / 1O consists of  
●  Three plugs 
●  one logic component 
●  one socket 
You can choose which of the eight possible input conditions an output signal should be 
generated for. 
The following are available: 
●  three truth tables (1 to 3) for the SIMOCODE pro C basic unit 
●  four truth tables (1 to 4) for the SIMOCODE pro S basic unit 
●  six truth tables (1 to 6) for the SIMOCODE pro V PB and pro V MB RTU basic units 
●  eight truth tables (1 to 6, 10, 11) for the SIMOCODE pro V PN and pro V EtherNet IP 
basic units. 
The following schematic shows the "Truth Table for 3I / 1O" logic modules: 
 
Figure 4-89  "Truth Table for 3I / 1O" logic modules