Parameters
4.1 Motor protection
SIMOCODE pro - Parameterize
38 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
4.1.2.5
Further overload protection parameters
Class
The Class (trip class) defines the maximum time within which SIMOCODE pro must trip from
cold at 7.2 times the current setting I
s
(motor protection to IEC 60947). SIMOCODE pro
meets the requirements of tolerance band E according to IEC / EN 60947-4-1 in respect of
the accuracy of the tripping times. Please note that with startups > "Class 10", the
permissible AC3 current of the contactor may have to be reduced (derated), i.e. you must
select a larger contactor.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000