Parameters 
  4.1 Motor protection 
SIMOCODE pro - Parameterize 
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
35 
Transformation ratio - active  
When using an interposing transformer, or if the main supply cable is looped several times 
through the current measuring module or the current / voltage measuring module, you can 
enter the transformation ratio of the interposing transformer. Activate the checkbox if you 
wish to use this option. The parameterized current setting continues to correspond here to 
the actual rated motor current and does not have to be converted. 
The transformation ratio is calculated from the ratio between the rated motor current [A] and 
the measured current [A] or any multiple of the ratio. 
 
Note 
This parameter is only available when using SIMOCODE
 pro V PB basic unit above 
 *E03*. 
Transformation ratio - primary  
Enter the primary current here, with the "Transformation ratio - active" checkbox activated. 
Range: 0 to 8191.875 (default: 0). 
Transformation ratio - secondary  
Enter the secondary current here, with the "Transformation ratio - active" checkbox 
activated. Range: 0 to 15 (default: 0).  
 
Set current Is2 
Setting ranges for current setting I
s
2 
Range: Depends on the selected current measuring module or current / voltage measuring 
module.  
Current setting I
s
2 when using a current measuring module or a 1st generation current / 
voltage measuring module: 
●  0.3 to 3 A (default: 0.3) 
●  2.4 to 25 A 
●  10 to 100 A 
●  20 to 200 A 
●  63 to 630 A 
Current setting I
s
1 when using a 2nd generation current / voltage measuring module: 
●  0.3 to 4 A (default: 0.3) 
●  3 to 40 A 
●  10 to 115 A 
●  20 to 200 A 
●  63 to 630 A