Parameters   
4.3 Monitoring functions 
  SIMOCODE pro - Parameterize 
132  Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
 
External ground-fault monitoring with a 3UF7510 ground-fault module and 3UL23 
residual current transformer 
Settings 
You can parameterize two different response levels (trip level, warning level) for monitoring 
the ground-fault current. 
If the ground-fault current exceeds the response level, the current limit monitoring will 
respond. 
See also "Tables of responses of SIMOCODE pro" in Chapter Important information 
(Page 7).  
 
 
Figure 4-32  "Ground-fault Monitoring" function block 
Trip level, warning level 
You can parameterize two different response levels (trip level, warning level) for monitoring 
the ground-fault current. 
If the ground-fault current exceeds the response level, the current limit monitoring will 
respond. 
 
30 mA to 40 A in steps of 10 mA (default: 1000 mA) 
20 mA to 40 A in steps of 10 mA (default: 500 mA)