Siemens SIMOCODE pro - External Ground-Fault Monitoring with a 3 UF7510 Ground-Fault Module and 3 UL23 Residual Current Transformer

Siemens SIMOCODE pro
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
132 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
4.3.1.6
External ground-fault monitoring with a 3UF7510 ground-fault module and 3UL23
residual current transformer
Settings
You can parameterize two different response levels (trip level, warning level) for monitoring
the ground-fault current.
If the ground-fault current exceeds the response level, the current limit monitoring will
respond.
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Figure 4-32 "Ground-fault Monitoring" function block
Trip level, warning level
You can parameterize two different response levels (trip level, warning level) for monitoring
the ground-fault current.
If the ground-fault current exceeds the response level, the current limit monitoring will
respond.
Trip level:
30 mA to 40 A in steps of 10 mA (default: 1000 mA)
Warning level:
20 mA to 40 A in steps of 10 mA (default: 500 mA)