Parameters   
4.3 Monitoring functions 
  SIMOCODE pro - Parameterize 
136  Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
 
I> (upper limit) 
Trip level, warning level 
When monitoring current limits I > (upper limit), two different response levels can be 
parameterized and monitored: I> (upper limit) trip level, I> (upper limit) warning level 
If the current of one or more phases exceeds the response level, current limit monitoring 
responds. 
 
0 to 1020 % of l
s 
 in steps of 4% (default: 0) 
0 to 1020 % of l
s 
 in steps of 4% (default: 0) 
Active status of trip and warning levels 
The trip level / warning level is active only when the motor is running, the startup procedure 
has been completed and there is no test position feedback (TPF) (run+). 
Here you can define how SIMOCODE pro will respond if the trip level is undershot. 
See also "Tables of responses of SIMOCODE pro" in Chapter Important information 
(Page 7). 
Table 4- 34  "Trip level" response for monitoring current limits I > 
Deactivated  X (d) 
0 to 25.5 s (default: 0.5 s)