Parameters   
4.2 Motor control 
  SIMOCODE pro - Parameterize 
74  Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
 
"Direct starter" control function 
Description 
SIMOCODE pro can switch a motor on and off with this control function.  
●  Start with "ON >" activates the QE1 internal contactor control. 
●  Stop with "OFF" deactivates the QE1 internal contactor control. 
The control commands can be issued to SIMOCODE pro from any control stations (see also 
the description of "control stations"). Thus, the inputs (plugs) must be connected to the 
corresponding sockets, preferably to the "Enabled control command" sockets. 
Every fault message causes the QE1 contactor control to be deactivated. 
 
 
Figure 4-15  Schematic of the "Direct starter" control function, "Protection / Control" function block