Parameters   
4.3 Monitoring functions 
  SIMOCODE pro - Parameterize 
140  Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
 
Voltage monitoring 
Description 
SIMOCODE pro supports two-phase undervoltage monitoring of either a three-phase 
network or a single-phase network for freely selectable limits. The response of 
SIMOCODE pro on reaching a prewarning level or trip level can be freely parameterized and 
delayed. 
Voltage measurement is performed using current / voltage measuring modules. This is 
based on the minimum voltage of all voltages U
min
.  
 
Note 
Please note that only phase voltages are available with SIMOCODE
 pro V 
version *E06*. If required, the line-to-
line voltage can be calculated from the phase voltage 
using the logic module "Calculator 1/2" as follows: Line
-to-line voltage = phase 
 * 1.73. 
 *E07* onward, either phase voltage or line-to-line voltage can be used as the 
 
 
Figure 4-34  "Voltage Monitoring" function block 
Furthermore, even when the motor is switched off, SIMOCODE pro can determine and 
signal the further availability of the feeder by measuring the voltage directly at the circuit 
breaker or at the fuses in the main circuit.