Parameters   
4.7 Standard functions 
  SIMOCODE pro - Parameterize 
216  Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
 
Power failure monitoring (UVO) 
Description 
The "Power Failure Monitoring (UVO)" function block is activated via the plug. This is 
performed via an external voltage relay that is connected to the function block via the binary 
inputs of SIMOCODE pro. 
Sequence (see timing charts below):  
1.  All contactors (QE) are disconnected immediately after the monitoring relay has been 
operated/the input has been activated (UVO). 
2.  If the voltage is restored within the "power failure time", the motor will be reset to its 
previous state. This can either take place immediately or with a time delay (restart time 
delay). 
3.  If the "power failure time" elapses before the voltage returns, the device signals a fault 
(UVO fault). 
Prerequisite: The SIMOCODE pro control voltage is buffered and not interrupted. 
In total, one "Power Failure Monitoring" function block is available for the pro V basic units.