Parameters   
4.8 Logic modules 
  SIMOCODE pro - Parameterize 
240  Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
 
Counters are integrated in the SIMOCODE pro system. These are activated via the plugs "+" 
or "-".  
The counter output switches to "1" when the preset limit is reached. The counter is reset with 
"Reset". 
The current actual value is available as a socket for further internal processing and can also 
be transmitted to the automation system.  
●  Plug +: Increases the actual value by 1 (maximum: limit). 
●  Plug –: Reduces the actual value by 1 (minimum: 0). 
●  Reset: Resets the actual value to 0. 
The counter consists of 
●  three plugs (input +, input – and reset) 
●  one logic component 
●  one socket 
●  One "Actual value" analog socket with the current value in the range between 0 and the 
limit. The value is retained even in the event of a power failure. 
The following are available: 
●  two counters (1 to 2) for the SIMOCODE pro C and pro S basic units 
●  four counters (1 to 4) for the SIMOCODE pro V PB and pro V MB RTU basic units 
●  six counters (1 to 6) for the SIMOCODE pro V PN and pro V EIP basic units.