Parameters 
  4.2 Motor control 
SIMOCODE pro - Parameterize 
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
111 
You will find detailed explanations of the settings in Chapter Application selection, settings 
and definitions of control functions  (Page 66). 
Table 4- 22  Positioner control function settings 
ON <  Control command ON < (CLOSED) (connection with any socket, usually with 
"Enabled control command - ON <" socket) 
OFF  Control command STOP (connection with any socket, usually with "Enabled 
control command - OFF" socket) 
ОN >  Control command ON (OPEN) (connection with any socket, usually with 
"Enabled control command - ON >" socket) 
FB ON  Auxiliary control input "Feedback ON" (connection with any socket, usually with 
"Status - current flowing" socket) 
FC  Auxiliary control input "Feedback CLOSED" (connection with any socket, 
usually with the socket of an input to which the limit switch is wired.) 
FO  Auxiliary control input "Feedback OPEN" (connection with any socket, usually 
with the socket of an input to which the limit switch is wired.) 
TC  Auxiliary control input "Torque CLOSED" (connection with any socket, usually 
with the socket of an input to which the torque switch is wired.) 
TO  Auxiliary control input "Torque OPEN" (connection with any socket, usually with 
the socket of an input to which the torque switch is wired.) 
Non-maintained command mode  
•  Deactivated (default setting) 
•  Activated 
Separate fail-safe function from control 
function 
•  Deactivated (default setting): A safety-related tripping by the DM-F modules 
is also effected by the SIMOCODE pro control function, avoiding additional 
follow-on fault messages. This setting is selected for applications where 
safety-related tripping directly affects the motor controlled by 
SIMOCODE pro. 
•  Activated: A safety-related tripping by the DM-F modules does not affect the 
SIMOCODE pro control function. This setting is selected for applications 
where safety-related tripping does not affect the motor controlled by 
SIMOCODE pro. 
Load type   You can choose between: 
•  Motor (default) 
•  Resistive load (see Chapter Application selection, settings and definitions of 
control functions  (Page 66)) 
Range 0 to 25.5 s (default: 0.5 s) 
Execution time   Time until the end position is reached. 
Range 0 to 6553.5 s (default: 1.0 s) 
Range 0 to 255 s (default: 0 s)