Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
158 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Response
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Overtemperature: Here you can select how SIMOCODE pro should respond when the
temperature has overshot the warning level / trip level.
Table 4- 48 "Overtemperature" response
Response
Warning level T >
Trip level T >
disabled
X
signaling X X
warn
X (d)
tripping X (d)
Note
With motors for EEx e applications, the response must be set to "tripping"!
Note
The sensor type, the number of measuring circuits in use and the response to a sensor fault
must be set in the Temperature module inputs (TM1
/ 2 inputs) function block if temperature
monitoring is used.
Note
To monitor several sensor measuring circuits individually and independently, a suitable
number of free limit monitors can be connected to the temperature module inputs (TM1
/ 2
inputs) fun
ction block and differing limits set for the individual temperature sensors, instead
of the temperature monitoring function block.