Parameters
4.8 Logic modules
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
271
Example - Pulse width modulator
A load will be switched on and off with a duration of 60 minutes, dependent on a measured
value (e.g., temperature).
If the measured value exceeds a maximum value of 50°°C (323 K), the load will be
switched on permanently, and if it falls below 20°°C (293 K), it will be switched off
permanently.
If the measured value falls within the range between the minimum and maximum value,
the On duration will be proportional to the measured value.
Duration: 60 min (3600 s)
Lower limit: 20°C (293 K)
Hi limit: 50°C (323 K).
At 20°C (293 K): OFF
At 30°C (303 K): 20 min ON and 40 min OFF
At 40°C (313 K): 40 min ON and 20 min OFF
At 50°C (323 K): ON.