Parameters
4.2 Motor control
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
71
Behavior of "feedback message ON"
1)
Figure 4-13 Execution time (ET) and feedback time (FT) in relation to FB ON
1)
Note
Behavior with a current less than 12 % of I
s
At a current less than 12% of the motor's
rated current I
e
, the "Current I_max (% of I
e
)' and
I_Lx (% of I
e
)" is indicated as 0 %. Equally, the binary "Status - Motor current
flowing" signal remains set to logical zero.
The contactor controls are deactivated.
The following signals are also output:
● A flashing signal on the QLS lamp control
● A flashing signal on the "GEN. FAULT" LED
● The "Status - General fault" signal
● The corresponding signaling bit of the fault.