Parameters   
4.2 Motor control 
  SIMOCODE pro - Parameterize 
96  Operating Manual, 04/2017, A5E40507630002A/RS-AA/001 
You will find detailed explanations of the settings in Chapter Application selection, settings 
and definitions of control functions  (Page 66). 
Table 4- 17  Control function settings for Dahlander reversing starter 
Dahlander reversing starter  
OFF  Control command OFF (Connection with any socket, usually with "Enabled 
control command OFF" socket) 
ON  Control command ON > (CW, SLOW) (connection with any socket, usually with 
"Enabled control command ON >" socket) 
ON >>  Control command ON >> (CW, FAST) (connection with any socket, usually with 
"Enabled control command ON >>" socket) 
ON <  Control command ON < (CCW, SLOW) (connection with any socket, usually 
with "Enabled control command - ON <" socket) 
ON <<  Control command ON << (CCW, FAST) (connection with any socket, usually 
with "Enabled control command ON <<" socket) 
FB ON  Auxiliary control input "Feedback ON" (connection with any socket, usually with 
"Status - current flowing" socket) 
Non-maintained command mode  
•  Deactivated (default setting) 
•  Activated 
Saving change-over command  
•  Deactivated (default setting) 
•  Activated 
Separate fail-safe function from control 
function 
•  Deactivated (default setting): A safety-related tripping by the DM-F modules 
also affects the SIMOCODE pro control function, avoiding additional follow-
on fault messages. This setting is selected for applications where safety-
related tripping directly affects the motor controlled by SIMOCODE pro. 
•  Activated: A safety-related tripping by the DM-F modules does not affect the 
SIMOCODE pro control function. This setting is selected for applications 
where safety-related tripping does not affect the motor controlled by 
SIMOCODE pro
 
Load type   You can choose between: 
•  Motor (default) 
•  Resistive load (see Chapter Application selection, settings and definitions of 
control functions  (Page 66)) 
Range 0 to 25.5 s (default: 0.5 s) 
Range 0 to 6553.5 s (default: 1.0 s) 
Range 0 to 255 s (default: 0 s) 
Range 0 to 655.3 s (10 ms steps) (default: 0.00 s)