SIMPRO-100
SIMPRO-100 Relay Settings Sheets
F
PRIM-2400C 217
Negative-Sequence O/C Pickup
Range: OFF, 0.25 – 100.00 A; ITAP = 5 A
Range: OFF, 0.05 – 20.00 A; ITAP = 1 A
50QP =
[OFF]
Negative-Sequence O/C Time Delay
Range: 0.10 – 400.00 s
50QD =
[Hidden]
F.1.4 Jogging Block Element
Settings
Maximum Number of Starts per Hour
Range: OFF, 1 – 15
MAXSTART =
[3]
Minimum Time Between Starts
Range: OFF, 1 – 150 min
TBSDLY =
[20]
F.1.5 Load-Jam Function
Settings
Load-Jam Trip Pickup
Range: OFF, 0.5 – 6.0 pu FLA
LJTPU =
[2.0]
Load-Jam Trip Delay
Range: 0.00 – 400.0 s
LJTDLY =
[1.00]
F.1.6 Load-Loss Element
Settings
(Hidden when voltage option available.)
Load-Loss Alarm Threshold
Range: OFF, 30 – 2000 W; ITAP = 5 A
Range: OFF, 6 – 400 W; ITAP = 1 A
LLAPU =
[OFF]
Load-Loss Trip Threshold
Range: 30 – 2000 W; ITAP = 5 A
Range: 6 – 400 W; ITAP = 1 A
LLTPU =
[100]
Load-Loss Starting Time Delay
Range: 0 – 15000 s
LLSDLY =
[0]
Load-Loss Alarm Time Delay
Range: 0.00 – 400.00 s
LLADLY =
[5.00]
Load-Loss Trip Time Delay
Range: 0.00 – 400.00 s
LLTDLY =
[10.00]
(Hidden when voltage option unavailable.)
Load-Loss Alarm Threshold
Range: OFF, 0.05 – 1.00 pu FLA
LLAPU =
[OFF]
Load-Loss Trip Threshold
Range: 0.05 – 1.00 pu FLA
LLTPU =
[0.5]
Load-Loss Starting Time Delay
Range: 0 – 15000 s
LLSDLY =
[0]