SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
109
The Power Modules PM240-2 FSD and FSE do not have integrated overcurrent protection
for the DC link. You must therefore use aR characteristics fuses.
Line voltage 3-phase 380 … 480 V AC
Table 5- 1 Fuses for Power Modules PM240-2 FSD
Article No.
without integrated line filter
with internal line filter
6SL3210–
1PE23-8UL0
1PE23-8AL0
6SL3210–
1PE24-5UL0
1PE24-5AL0
6SL3210–
1PE26-0UL0
1PE26-0AL0
6SL3210–
1PE27-5UL0
1PE27-5AL0
Rated current
A
100
100
125
125
Table 5- 2 Fuses for Power Modules PM240-2 FSE
Article No.
without integrated line filter
with internal line filter
6SL3210–
1PE28-8UL0
1PE28-8AL0
6SL3210–
1PE31-1UL0
1PE31-1AL0
The PM240-2 Power Modules cannot feed back regenerated energy into the line supply. For
regenerative operation, e.g. the braking of a rotating mass, a braking resistor must be
connected to convert the resulting energy into heat.
A thermostatic switch monitors the braking resistor for overtemperature and issues a signal
on an isolated contact if the limit value is exceeded.