Blocksize Power Modules (PM240-2)
4.6 Technical data
SINAMICS S110
100 Manual, 07/2015, 6SL3097-4AC10-0BP5
Table 4- 21 Technical data of the PM240-2, FSA (400 V) (1/2)
Line voltage 3-phase 380 … 480 V AC ± 10%
Article No.
without integrated line filter
with integrated line filter
6SL3210–
1PE11-8UL1
1PE11-8AL1
6SL3210–
1PE12-3UL1
1PE12-3AL1
6SL3210–
1PE13-2UL1
1PE13-2AL1
6SL3210–
1PE14-3UL1
1PE14-3AL1
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
max
A
A
A
1.7
1.3
2.0
2.2
1.7
2.5
3.1
2.2
3.5
4.1
3.1
4.5
1)
on basis of I
n
kW
0.55
0.75
1.1
1.5
Rated pulse frequency
Max. Pulse frequency
kHz
4
4
4
4
Sound pressure level LpA (1 m)
2)
of the external
Ω ≥ 370 ≥ 370 ≥ 370 ≥ 370
Max. Cable length
to the braking resistor
L1, L2, L3,
Screw-type terminals
Cross head M2.5
Conductor cross section: 1.5 … 2.5 mm
2
Tightening torque: 0.5 Nm
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
3)
Without line filter
kg
1.4
1.4
1.4
1.4
Rated output of a typical standard induction motor at 400 V.
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
To observe the limit values of EN 61800-3 category C2, for Power Modules PM240-2 with integrated line filter 50 m
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power
Module with an external line filter class B and a motor reactor.