DC link components
5.2 Braking resistors
SINAMICS S110
116 Manual, 07/2015, 6SL3097-4AC10-0BP5
Technical data
Line voltage 1/3-phase 200 V AC -10 % to 240 V AC +10 %:
Note
Use the following or
comparable braking resistors for the PM240-2 Power Modules 200 V.
The technical properties and statements made by the manufacturer apply.
Table 5- 4 Braking resistors for Blocksize PM240-2, 200 V, FSA - FSC
Company Heine Resistors GmbH
Manufacturer's designation
GWHS
167-60x30-K
IP20 200. ±7%
37.5 W TS KA
100 cm
GWHS
217-60x30-K
IP20 68. ±7%
110 W TS KA
100 cm
GWHS
337-60x30-K
IP20 37. ±7%
200 W TS KA
100 cm
Manufacturer's Article No.
DB
Load duration for peak power T
a
s 12 12 12
Period duration of braking duty cycle
s 240 240 240
Power connections
(including PE)
Max. connectable cross-section:
2.5 mm
2
4.0 mm
2
6.0 mm
2
Thermostatic switch
Max. connectable cross-section:
2.5 mm
2
2.5 mm
2
2.5 mm
2
Thermostatic switch (NC contact)
Maximum contact load
250 V AC / 2.5 A 250 V AC / 2.5 A 250 V AC / 2.5 A
Matching Power Modules
1)
6SL3210-
1PB13-0xL0
1PB13-8xL0
6SL3211-
6SL3210-
1PB15-5xL0
1PB17-4xL0
1PB21-0xL0
6SL3211-
6SL3210-
1PB21-4xL0
1PB21-8xL0
6SL3211-
Unit rating of the Power Module
1)
x = A: Power Module with integrated line filter, x = U: Power Module without integrated line filter