Mains connection and line-side power components
3.7 Line filter
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
51
Table 3- 11 Connecting Power Module PM240-2 to the line filter
FSB 4 x M4 bolts 2.5 Nm
Table 3- 12 Technical data of line filter Blocksize PM240-2
Line voltage 3-phase 380 to 480 V AC
Line supply connection
L1, L2, L3
Max. cross section that
can be connected: 2.5
mm
2
Tightening torque:
Max. cross section that
can be connected: 6 mm
2
Tightening torque:
1.5 … 1.8 Nm
Max. cross section that
can be connected: 16
mm
2
Tightening torque:
Line supply connection
Cable (including PE') on the line filter
PE connection
Max. cross section that
can be connected: 2.5
mm
2
Tightening torque:
Max. cross section that
can be connected: 6 mm
2
Tightening torque:
2.0 ±0.1 Nm
Max. cross section that
can be connected: 16
mm
2
Tightening torque:
Suitable for Power Module 6SL3210-
1PE11-8UL1
1PE12-3UL1
1PE13-2UL1
1PE14-3UL1
1PE16-1UL1
1PE18-0UL1
6SL3211-
6SL3210-
1PE21-1UL0
1PE21-4UL0
1PE21-8UL0
6SL3211-
6SL3210-
1PE22-7UL0
1PE23-3UL0
6SL3211-
Unit rating of the Power Module