Blocksize Power Modules (PM240-2)
4.5 Mounting
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
93
4.5
Mounting
4.5.1
Mounting instructions
Note
Mounting instructions
Please refer to the notes for installing Power Modules in Section Safety instructions for
Blocksize Power Modules (PM240-2) (Page 70).
You must mount the PM240-2 Push Through Power Modules on an unpainted metal
surface in order to comply with EMC requirements.
To be able to mount PM240-2 Push Through Power Modules, the wall thickness of the
cabinet must be 3.5 mm.
Note
Installation frame for push through units
An installation frame should be used when push through units are installed in the cabinet.
You can find more information about the installation frame in Section
Mounting frame
(Page
222).
This mounting frame includes the necessary seals and frame to ensure compliance with
degree of protection IP54.
If you do not use the mounting frames, yo
u must ensure that the required degree of
protection is complied with using other appropriate measures.