Table 3- 14 Technical data line reactors PM240-2 FSA to FSC
Rated current A 4.0 11.3 22.3 47.0
Line/load connection
1L1, 1L2,1L3
2L1, 2L2, 2L3
Max. cross section
that can be connect-
ed: 2.5 mm
2
Tightening torque:
Max. cross section
that can be con-
nected: 2.5 mm
2
Tightening torque:
Max. cross section
that can be con-
nected: 6 mm
2
Tightening torque:
Max. cross section
that can be con-
nected: 16 mm
2
Tightening torque:
PE connection Type: M4 bolts
Tightening torque: 3
Type: M4 bolts
Tightening torque: 3
Type: M5 bolts
Tightening torque: 5
Type: M5 bolts
Tightening torque: 5
Matching Power Mod-
ules
1)
Line voltage 1/3 AC 200 V -10 % to 240 V +10 %:
6SL3210-
1PB13-0xL0
1PB13-8xL0
6SL3211-
6SL3210-
1PB15-5xL0
1PB17-4xL0
1PB21-0xL0
6SL3211-
6SL3210-
1PB21-4xL0
1PB21-8xL0
6SL3211-
Line voltage 3-phase 380 V AC -10% to 480 V AC +10%:
6SL3210-
1PE11-8xL1
1PE12-3xL1
1PE13-2xL1
6SL3210-
1PE14-3xL1
1PE16-1xL1
1PE18-0xL1
6SL3211-
6SL3210-
1PE21-1xL0
1PE21-4xL0
1PE21-8xL0
6SL3211-
6SL3210-
1PE22-7xL0
1PE23-3xL0
6SL3211-
Unit rating of the Power
kW 0.55 … 1.1 1.1 … 3.0 3.0 … 7.5 5.5 … 15
1)
x = A: Power Module with integrated line filter, x = U: Power Module without integrated line filter