System overview
2.5 Derating
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
31
2.5
Derating
The Power Modules are designed for operation under the following conditions:
Installation altitude up to 1000 m above sea level
Ambient temperature 0 °C to 40 °C
Rated pulse frequency according to the Technical Data of the Power Module
Output frequency above 22 Hz (FSA - FSC) or 10 Hz (FSD - FSE)
Derating as a function of the installation altitude
The air pressure and therefore the air density are lower at higher altitudes above mean sea
level (MSL). The same quantity of air does not have the same cooling effect and the
clearance between 2 electrical conductors can only isolate a lower voltage. Typical values
for air pressure are summarized in the table below:
Table 2- 4 Air pressure for various installation altitudes
Installation altitude above
sea level in [m]
0 1000 2000 3000 4000
Installation altitude above
sea level in [ft]
0 3280 6561 9842 13123
Air pressure in mbar [kPa]
100
90
80
70
62
If the Power Modules are operated at installation altitudes > 1000 m above sea level, you
must reduce the maximum possible output current as follows:
Figure 2-3 Reduction of the output current as a function of the installation altitude above sea level
A TN or TT system with grounded neutral point is required (no grounded line conductor) for
installation altitudes above 2000 m. If the neutral point is not grounded, you must connect an
isolating transformer upstream, the secondary side of which is then grounded at the neutral
point.
A reduction of the line voltage phase-phase is not necessary.