EasyManua.ls Logo

Siemens SINAMICS S110 - Mains connection and line-side power components; Introduction

Siemens SINAMICS S110
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
35
Mains connection and line-side power components
3
3.1
Introduction
You should use the following line-side components to connect a SINAMICS Blocksize drive
line-up to the supply network:
Line disconnector
Overcurrent protection device (line fuse or circuit breaker)
Line contactor (this is required for galvanic isolation)
Line filter (only necessary to achieve EMC category C1 for Power Modules PM240-2 of
frame sizes FSA, FSB, and FSC)
Line reactor (only necessary for Power Modules PM240-2 FSA, FSB, and FSC)
Possible supply voltages for the drive line-up are:
For Power Modules PM240-2 FSA, FSB, and FSC:
1/3 AC 200 ... 240 V ± 10 %
3 AC 380 ... 480 V ± 10 %
For Power Modules PM240-2 FSD and FSE:
3 AC 380 ... 480 V -20/+10 %
Available line reactor variants:
External line reactors (Page 57) for PM240-2 Power Modules, frame sizes FSA to FSC
In Power Modules PM240-2 frame sizes FSD and FSE, the line reactors are integrated.
Available line filter variants:
Integrated (to achieve EMC category C2 or C3)
External (to achieve EMC category C1)
Figure 3-1 Example of a line connection for Power Modules Blocksize with no integrated line filter