X524 Electronics power supply
Table 8- 17 X524: Electronics power supply
Voltage: 24 V (20.4 … 28.8 V)
Current consumption: Max. 0.35 A
Maximum current via jumper in connector: 20 A (15 A
according to UL/CSA)
M Electronics ground
Type: Screw-type terminal (Page 263)
Max. cross section that can be connected: 2.5 mm²
The maximum cable length that can be connected is 30 m.
Note
The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
Connection examples
Connection example 1: HTL encoder, bipolar, with reference signal
Figure 8-12 Connection example 1: HTL encoder, bipolar, with reference signal
Signal cables must be twisted in pairs to improve immunity to induced noise.