CU305 Control Units
7.3 Interface description
SINAMICS S110
146 Manual, 07/2015, 6SL3097-4AC10-0BP5
7.3.5.4
X100 DRIVE-CLiQ interface
Table 7- 15 X100 DRIVE-CLiQ interface
Pin
Signal name
Technical data
1
TXP
Transmit data +
2
TXN
Transmit data -
3
RXP
Receive data +
4 Reserved, do not use
5
Reserved, do not use
6
RXN
Receive data -
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
Power supply
B
M (0 V)
Electronics ground
Connector type
DRIVE-CLiQ socket
The blanking cover for the DRIVE
-CLiQ port is included in the scope of delivery.
Blanking covers (50 x) Article No:: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE
-CLiQ cable length is 100 m.
7.3.5.5
X124 Electronics power supply
Table 7- 16 X124 electronics power supply
Terminal
Function
Technical data
+
Electronics power supply
Voltage: 24 V DC (20.4 to 28.8 V)
Current consumption: max. 0.8 A (incl. 0.35
A for HTL encoders, without DRIVE-CLiQ
and digital outputs)
Max. current via jumper in connector: 20 A
(15 A according to UL/CSA)
+
Electronics power supply
M
Electronics ground
M Electronics ground
Type: Screw-type terminal (Page 263)
Max. cross section that can be connected: 2.5 mm
2
The maximum cable length that can be connected is 30 m.
Note
The two "+" or "M" terminals are jumpe
red in the connector. This ensures that the supply
voltage is looped through.