Supplementary system components and encoder system integration
8.4 Sensor Module Cabinet-Mounted SMC30
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
199
Table 8- 18 Meaning of LEDs on the Sensor Module Cabinet SMC30
RDY
READY
– Off The electronics power supply is missing or outside the per-
missible tolerance range.
–
Green Continu-
ous light
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
–
Orange Continu-
DRIVE-CLiQ communication is being established. –
Red Continu-
ous light
This component has at least one fault.
LED is controlled independently of any reconfiguration of the
Remedy and
acknowledge fault
Green/red Flashing
light 0.5
Firmware is being downloaded. –
Green/red Flashing
Firmware download is complete. The system waits for
Carry out a POWER
Green/
orange
or
Red/
Flashing
light
Component recognition via LED is activated
1)
.
Both options depend on the LED status when component
recognition is activated.
–
OUT >
5 V
– Off The electronic power supply is missing or outside permissi-
ble tolerance range.
–
Orange Continu-
ous light
The electronics power supply for the encoder system is
available.
–
1)
Data on the parameters for activating the component recognition via LED, see SINAMICS S110 List Manual
Damage to the encoder electronics due to incorrect voltage supply
If an encoder that is designed for a 5 V supply is operated with a 24 V supply, this can
destroy the encoder electronics.
• Make sure that the connected encoder can be operated with a 24 V power supply.
Cause and rectification of faults
The following documents contain information about the cause of faults and how they can be
rectified:
● SINAMICS S110, Function Manual
● SINAMICS S110, List Manual