Supplementary system components and encoder system integration
8.4 Sensor Module Cabinet-Mounted SMC30
SINAMICS S110
202 Manual, 07/2015, 6SL3097-4AC10-0BP5
8.4.8
Protective conductor connection and shield support
Shield contacts are only required if the system is connected to X521/X531.
PE conductor connection M4 / 1.8 Nm
Shield connection terminal, Weidmüller company, type: KLBÜ CO1, Article No.: 1753311001
Figure 8-17 Shield support and PE conductor connection
The bending radii of the cables must be observed (see MOTION-CONNECT description).
NOTICE
Damage or faulty operation due to incorrect shielding or inadmissible cable lengths
If the correct shielding procedures or the permissible cable lengths are not observed, it can
cause damage or the machine may malfunction.
Only use shielded cables.
Do not exceed the cable lengths stated in the technical data.