EasyManua.ls Logo

Siemens SINAMICS S110 - Line contactors

Siemens SINAMICS S110
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mains connection and line-side power components
3.6 Line contactors
SINAMICS S110
42 Manual, 07/2015, 6SL3097-4AC10-0BP5
3.6
Line contactors
A line contactor is required if the drive line-up needs to be electrically isolated from the
power supply.
The characteristic values in the technical data apply when the line contactor is selected. You
must consider the type of routing, the bundling factor, and the factor for the ambient
temperature according to EN 60204-1 when dimensioning the conductors to be connected.
NOTICE
Damage to the drive electronics when switching the line contactor under load
If you switch the line contactor (recommended type) under load, the contacts will wear out
prematurely. This may lead to faulty functioning of the contactor with subsequent damage
to the drive electronics.
Use a leading auxiliary break contactor and/or use a Voltage Sensing Module (VSM10).
If this is not possible, avoid switching the line contactor under load.
Note
To limit the switching overvoltage, the contactor coil must be connected to an overvoltage
limiter (e.g. freewheeling diode or varistor).
When the digital output is used to control the line contactor, you must consider the
make/break capacity.

Table of Contents

Other manuals for Siemens SINAMICS S110

Related product manuals