Blocksize Power Modules (PM240-2)
4.6 Technical data
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
97
Table 4- 18 Technical data of the PM240-2, FSA (200 V)
Line voltage 1/3 AC 200 ... 240 V ± 10 %
Article No.
without integrated line filter
with integrated line filter
6SL3210–
1PB13-0UL0
1PB13-0AL0
6SL3210–
1PB13-8UL0
1PB13-8AL0
6SL3211–
1PB13-8UL0
1PB13-8AL0
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
max
A
A
A
3.0
2.3
3.3
3.9
3.0
4.3
3.9
3.0
4.3
1)
on basis of I
n
kW
0.55
0.75
0.75
Rated pulse frequency
Max. Pulse frequency
kHz
4
4
4
4)
Sound pressure level LpA (1 m)
2)
of the external
Ω ≥ 200 ≥ 200 ≥ 200
Max. Cable length
to the braking resistor
Line supply connection L1, L2, PE
Screw-type terminals
Cross head M2.5
Conductor cross section: 1.5 … 2.5 mm
2
Tightening torque: 0.5 Nm
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
3)
IP20 in the cabinet: IP20
Without line filter
kg
1.4
1.4
1.8
Rated output of a typical standard induction motor at 230 V.
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
To observe the limit values of EN 61800-3 category C2, for Power Modules PM240-2 with integrated line filter 50 m
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power
Module with an external line filter class B and a motor reactor.
4)
Power loss in the cabinet: 0.02 kW. The remaining power loss is dissipated through the heat sink.