Blocksize Power Modules (PM240-2)
4.6 Technical data
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
99
Table 4- 20 Technical data of the PM240-2, FSC (200 V)
Line voltage 1/3 AC 200 ... 240 V ± 10 %
Article No.
without integrated line filter
with integrated line filter
6SL3210–
1PB21-4UL0
1PB21-4AL0
6SL3210–
1PB21-8UL0
1PB21-8AL0
6SL3211–
1PB21-8UL0
1PB21-8AL0
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
max
A
A
A
13.6
10.4
15.0
17.5
13.6
19.3
17.5
13.6
19.3
1)
on basis of I
n
kW
3.0
4.0
4.0
Rated pulse frequency
Max. Pulse frequency
kHz
4
4
4
4)
Sound pressure level LpA (1 m)
2)
Resistance value of the external braking resistor
Max. Cable length
to the braking resistor
Line supply connection L1, L2, PE
Screw-type terminals
Cross head M4
Conductor cross section: 6 … 16 mm
2
Tightening torque: 1.3 Nm
Motor connection U2, V2, W2
DC-link connection, connection for braking
resistor
DCP/R1, DCN, R2
3)
IP20 in the cabinet:
IP20
Without line filter
kg
5.0
5.0
5.8
Rated output of a typical standard induction motor at 230 V.
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
To observe the limit values of EN 61800-3 category C2, for Power Modules PM240-2 with integrated line filter 50 m
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power
Module with an external line filter class B and a motor reactor.
4)
Power loss in the cabinet: 0.075 kW. The remaining power loss is dissipated through the heat sink.