CU305 Control Units
7.3 Interface description
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
137
Table 7- 6 PROFIBUS/USS address switch
Technical data
Switch
Significance
S1
2
0
= 1
S2 2
1
= 2
S3
2
2
= 4
S4 2
3
= 8
S5
2
4
= 16
S6
2
5
= 32
S7 2
6
= 64
Setting the PROFIBUS address
1. Setting via the corresponding parameters (see SINAMICS S110 List Manual)
The STARTER is used to set the bus address for a PROFIBUS node to a value
between 1 and 126. This is only possible if the address switch is set to 0 or 127
(factory setting).
2. Manual setting
The address switch (DIP switch) is used to manually set the bus address to a value
between 1 and 126. In this case, the parameter is only used to read the address.
Setting the USS address
1. Setting via the corresponding parameters (see SINAMICS S110 List Manual)
The STARTER is also used to set the bus address for USS nodes to a value between
0 and 30. This is only possible if the address switch is set to 0 or 127 (factory setting).
2. Manual setting
The address switch (DIP switch) is used to manually set the address to a value
between 0 and 30. If addresses are set manually to values >30, the setting will revert
to the value set in the parameter or the default value.
Note
A value of 0 is used as the address for USS if no other address has been saved in the
parameter.