CU305 Control Units
7.3 Interface description
SINAMICS S110
142 Manual, 07/2015, 6SL3097-4AC10-0BP5
We always recommend that bipolar encoders are used.
When using unipolar encoders the unused negative track signals can either be left
unconnected or connected to ground. This results in different switching thresholds.
Table 7- 11 Specification, measuring systems that can be connected
Permissible signal level in
bipolar mode
1)
;
(TTL, SSI, HTL bipolar at
2)3)
U
diff
V 2.0 V
CC
Permissible signal frequency
min
Permissible zero pulse (with T
s
= 1/f
s
)
Center of the
pulse posi-
Degrees 50 135 220
Switching threshold in the
unipolar mode
1)
and signals
AN_SSI_XDAT, BN, RN at X23
U
(Switch)
4)
V Low
4)
3.5 4.8 6.3
Operating points in unipolar
mode
1)
and signals
AN_SSI_XDAT, BN, RN not
U
(Switch)
4)
V Low
4)
5.9 7.9 10.2
For the relevant parameters for setting the mode, see the SINAMICS S110 List Manual
Other signal levels according to the RS422 specification.
The absolute level of the individual signals varies between 0 V and V
CC
of the measuring system.
For the relevant parameters for setting the switching threshold, see the SINAMICS S110 List
Note
Prefabricated cable for 5 V TTL encoder
If a
5 V TTL encoder (6FX encoder) is used, the connecting cable 6FX8002-2CR00-.... has