CU305 Control Units
7.5 Meaning of LEDs
SINAMICS S110
160 Manual, 07/2015, 6SL3097-4AC10-0BP5
COM
CU305 DP
CU305 PN
- Off Cyclic communication is not (yet) running.
The PROFIdrive is ready for communication
when the Control Unit is ready for operation
-
Green
Cyclic communication is taking place.
0.5 Hz
Full cyclic communication is not yet in progress.
2)
-
Red 0.5 Hz
flashing light
The PROFIBUS master is sending a faulty pa-
rameter assignment or the configuration is incor-
rect.
Modify the configura-
tion between mas-
ter/controller and
2 Hz
Cyclic bus communication has been interrupted
or could not be established
Rectify the bus com-
COM
CU305 CAN
- Off Electronics power supply is missing or outside
permissible tolerance range.
Communication board defective or not inserted.
-
Green
2.5 Hz
PREOPERATIONAL
No PDO communication possible.
-
Single flash STOPPED
Only NMT communication possible.
-
Red Continuous light BUS OFF Check the baud rate
Single flash ERROR PASSIVE MODE
The error counter for "error passive" has reached
Check the baud rate
and cabling.
Double flash Error Control Event
A guard event has occurred.
Check the connection
OUT > 5 V
Orange Continuous light The voltage of the electronics power supply for
the measuring system is 24 V.
3)
-
Operating state (reserved)
For activation of component recognition via LED, see the SINAMICS S110 List Manual
Possible causes:
- The controller is not transferring any setpoints.
- For isochronous operation, there is either no GC (Global Control) transferred from the controller, or it has an error.
3)
Only encoders that are rated for a voltage of 24 V must be connected.