Cabinet design and EMC for components, Blocksize format
10.7 Notes on electrical cabinet cooling
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
241
NOTICE
Damage caused by overheating
Overheating can cause system damage.
Install the components with the specified orientation.
Maintain the minimum clearances to other components.
Install suitable ventilation in the cabinet to dissipate the power loss of the individual
components.
Install suitable air filters and keep the heat sink clean.
Ensure that the components are provided with adequate cooling air through the cooling
openings. In particular, the connected signal and power cables must not cover the
ventilation openings.
Ensure that the cooling air flow is not blocked by other devices or mix with the exhaust
air from other devices. If necessary, insert air baffles.
Cooling unit
Cabinet
Figure 10-3 Examples of cabinet ventilation