Mains connection and line-side power components
3.3 Overcurrent protection by means of line fuses and circuit breakers
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
39
Table 3- 7 Fuses for Power Modules PM240-2 FSC
Article No.
without integrated line filter
with internal line filter
6SL3210–
1PE22-7UL0
1PE22-7AL0
6SL3210–
1PE23-3UL0
1PE23-3AL0
6SL3211–
1PE23-3UL0
1PE23-3AL0
Rated current
Short-circuit current rating
A
50
50
50
Table 3- 8 Fuses for Power Modules PM240-2 FSD
Article No.
without integrated line filter
with internal line filter
6SL3210–
1PE23-8UL0
1PE23-8AL0
6SL3210–
1PE24-5UL0
1PE24-5AL0
6SL3210–
1PE26-0UL0
1PE26-0AL0
6SL3210–
1PE27-5UL0
1PE27-5AL0
Rated current
Short-circuit current rating
A
60
70
90
100
1)
2)
Line protection
2)
Line protection and protection of the Power Module
Table 3- 9 Fuses for Power Modules PM240-2 FSE
Article No.
without integrated line filter
with internal line filter
6SL3210–
1PE28-8UL0
1PE28-8AL0
6SL3210–
1PE31-1UL0
1PE31-1AL0
Rated current
Short-circuit current rating
SCCR
A
kA
125
65
150
65
1)
2)
Line protection
2)
Line protection and protection of the Power Module