Blocksize Power Modules (PM240-2)
4.2 Safety instructions for Blocksize Power Modules (PM240-2)
SINAMICS S110
72 Manual, 07/2015, 6SL3097-4AC10-0BP5
Material damage caused by loose power connections
Insufficient tightening torques or vibration can result in faulty electrical connections. This
can cause fire damage or functional faults.
• Tighten all power connections with the specified tightening torques, e.g. line supply
connection, motor connection, DC-link connections.
• Check the tightening torques of all power connections at regular intervals and tighten
them when required. This applies in particular after transport.
• In the case of plug-in power terminals, check that the interlock of the connectors on the
converter housing is intact.
Note
Malfunctions on non-Siemens equipment caused by high-frequency faults in residential
environments
In the first environment, Category C2 according to EMC product standard IEC 61800
-3
(residential, commercial and industrial sector), the device may cause high
-frequency
disturbance, which can result in malfunct
ions in other equipment.
Have the installation and commissioning with appropriate radio interference suppression
measures preformed by qualified personnel.
Note
Connection approval for Power Modules ≤ 16 A per conductor
Power Modules have been designed for use in the industrial environment and generate
current harmonics on the line side as a result of the rectifier circuit.
-in Power Modules ≤ 16 A per conductor must meet the current
harmonics requirements of EN 61000
-3-2 to be connected to the public low-voltage power
If they do not, a connection approval must be applied for from the competent power utility.
-approved system use UL-approved cables only.