PLC commissioning
6.3 Creating a SIMATIC S7 project
Manual
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
169
6.3.7 Parameterizing the MPI interface (X102) (optional)
The interface X102 needs to be networked only with MPI, if the interface is not networked
with PROFIBUS.
When you have completed the "Properties - PROFIBUS DP Interface" dialog box (see
previous Subsection
"Parameterizing the PROFIBUS interface (X101)" (Page 165)) the
840Di sl Rack is displayed in the Station window.
To parameterize the MPI interface you will have to make the following parameter settings:
Interface type
Transmission rate
By double-clicking the module
MPI/DP
, slot
X1
in the 840Di sl-rack, open the properties
dialog of MPI/DP.
Dialog
Dialog: MPI/DP Properties
Tab: General
Group: Interface
Type: MPI
Button: "Properties..."
Dialog: Properties - PROFIBUS interface MPI/DP
Tab: Parameter
address: 2 (see note)
Subnet: MPI(1) 187.5 kBaud
OK
OK
NOTICE
With SINUMERIK 840Di sl, the MPI address of the PLC must always be set to 2.