Hardware Descriptions
2.12 PP72/48 I/O module
Manual
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
95
PROFIBUS address (S1)
The PROFIBUS address of the ADI4 can be set in the range 1 to 127 using switch S1.
Table 2-16 Meaning of switch S1
switch Description
1 PROFIBUS address: 2
0
= 1
2 PROFIBUS address: 2
1
= 2
3 PROFIBUS address: 2
2
= 4
4 PROFIBUS address: 2
3
= 8
5 PROFIBUS address: 2
4
= 16
6 PROFIBUS address: 2
5
= 32
7 PROFIBUS address: 2
6
= 64
8 Not used
NOTICE
A newly set PROFIBUS address will only come into effect after power OFF/ON.
Digital inputs/outputs (X111/X222/X333)
Interface description of the digital input/output interfaces (X111/X222/X333):
● Connectors: 50-pin ribbon cable connector
● Pin assignment on each connector.
Table 2-17 Pin assignment (X111/X222/X333)
Pin Signal designation Type
1)
Pin Signal designation Type
1)
1 M VO 26 Input 2.7 I
2 P24OUT VO 27 - -
3 Input 0.0 I 28 - -
4 Input 0.1 I 29 - -
5 Input 0.2 I 30 - -
6 Input 0.3 I 31 Output 0.0 O
7 Input 0.4 I 32 Output 0.1 O
8 Input 0.5 I 33 Output 0.2 O
9 Input 0.6 I 34 Output 0.3 O
10 Input 0.7 I 35 Output 0.4 O
11 Input 1.0 I 36 Output 0.5 O
12 Input 1.1 I 37 Output 0.6 O
13 Input 1.2 I 38 Output 0.7 O
14 Input 1.3 I 39 Output 1.0 O
15 Input 1.4 I 40 Output 1.1 O