Hardware Descriptions
2.12 PP72/48 I/O module
Manual
98 Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
33
H[WSRZHUVXSSO\
9VWDELOL]HG
9
9
;;;
3LQQXPEHU
'2&20[
5HOD\V
'ULYHUV
'ULYHUV
'ULYHUV
:
:
:
:
1
(M)
0
Figure 2-24 Terminal assignment for the digital outputs
● Connection cable: The required connecting cables (ribbon cables) must be provided by
the user
.
● Supply voltage:
To supply the digital outputs, an external 24V DC power supply must be connected to
DOCOMx (X111, X222, X333: Pin 47, 48, 49, 50).
The reference ground of the external power supply source must be connected to X111,
X222, X333: Pin 1 (M)
For further data, see Subsection
"Power Supply" (Page 100).
CAUTION
It is the user's responsibility to ensure that the max. current consumption per DOCOMx
pin (X111, X222, X333: Pins 47, 48, 49, 50) does not exceed 1 A. The power supply
(+24 V DC) for the digital outputs must therefore be connected to all 4 pins (X111, X222,
X333: Pin 47, 48, 49, 50) for each DOCOMx.
● Electrical specification of the digital outputs:
Table 2-19 Electrical specification of the digital outputs
Digital outputs min. Standard Max. Nominal
Voltage at high signal level (U
H)
V
CC
- 3 V
1)
V
CC
24V
Output current I
OUT
- - 250mA -
Voltage at low signal level (U
L)
- - - Output open
Leakage current at low level - 50mA 400mA -
Signal delay time T
PHL
2)