Functions
6.8 [2.09] Settings > Inputs/outputs
Operating with the Local User Interface
Operating Manual, 06/2017, A5E31930478-05
157
Table 6- 27 Function (pre-selection) "Fault"
Purpose/resulting settings
Fault Signal fault.
1. "Function" parameter box: Authorize access with corresponding PIN, if
necessary.
2. Set "Fault" value.
Table 6- 28 Function (pre-selection) "Maintenance alarm", "Maintenance demanded", and "Mainte-
nance required"
Purpose/resulting settings
Maintenance... Signal maintenance alarm, maintenance demanded or maintenance required:
1. "Function" parameter box: Authorize access with corresponding PIN, if
necessary.
2. Set the required message level.
Table 6- 29 Function (pre-selection) "Limit"
Purpose/resulting settings
Limits Signal limit violation
1. "Component" parameter box:
– Authorize access with corresponding PIN, if necessary.
– Select available component.
2. "Function" parameter box:
Select one of the two assigned limits.
Table 6- 30 Function (pre-selection) "Ext. warning limit"
Purpose/resulting settings
Ext. warning limit Monitor with an external warning limit.
1. "Function" parameter box:
Authorize access with corresponding PIN, if necessary.
2. Set one of the eight assigned external warning limits.