Connection for surface-mounted
housing
at bottom side of the console housing
Optical wavelength λ = 820 nm
Laser class 1 according to EN
60825-1/-2
Using glass fiber 50/125 μm or
Using glass fibre 62.5/125 μm
Permissible optical signal attenuation Max. 8 dB, with glass fibre 62.5/125 μm
Maximum transmission distance max. 1.5 km
Character idle state Selectable, factory setting“Light off”
Profibus RS485 DP
Connection for flush-mounted housing rear panel, slot “B”,
9-pole D-subminiature female connector
Connection for surface-mounted
housing
at the bottom side of the console housing
9-pole D-subminiature female connector
Test voltage 500 V; 50 Hz
Transmission rate bis 12 MBaud
Transmission distance 1000 m at ≤ 93.75 kBaud
500 m at ≤ 187.5 kBaud
200 m at ≤ 1.5 MBaud
100 m at ≤ 12 MBaud
Profibus FO DP
FO connector type ST connector single ring / double ring
FMS: depending on ordered version;
DP: only double ring available
Connection for flush-mounted housing rear panel, slot “B”
Connection for surface-mounted
housing
Please use the version with Profibus RS485 in the console housing and a sepa-
rate electrical/ optical converter.
Transmission rate Conversion by means of external OLM up to 1.5 MBaud
≥ 500 kBaud for normal version
≤ 57600 Baud with detached operator panel
Recommended transmission rate: > 500 kBaud
Optical wavelength λ = 820 nm
Laser class 1 according to EN
60825-1/-2
Using glass fiber 50/125 μm or
Using glass fibre 62.5/125 μm
Permissible optical signal attenuation Max. 8 dB, with glass fibre 62.5/125 μm
Transmission distance between two
modules with redundant optical ring
topology and glass fibre 62.5/125 m
2 m with plastic fibre
500 kBit/s max. 1.6 km
1500 kBit/s 530 m
Character idle state (status for “No
character”)
Light OFF
Max. number of modules in optical
rings with 500 kB/s or 1500 kB/s
41
DNP3.0/MODBUS RS485
Connection for flush-mounted housing rear panel, slot “B”,
9-pole D-subminiature female connector
Connection for surface-mounted
housing
in console housing
Test voltage 500 V; 50 Hz
Transmission rate up to 19200 Baud
Transmission distance max. 1 km
Technical Data
4.1 General
SIPROTEC 4, 7VE61 and 7VE63, Manual 197