Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
147
Receiving process typicals
(Cmd01B_R, Set01W_R, Par12D_R)
Program the value 0 if the typical is to receive data from more than one
partner, e.g. if it is to receive data from several control centers.
If the CPU receives data for this typical and "PartnerNo" is > 0, a check is
made to establish whether the source subscriber number in the data frame
is identical to the "PartnerNo" programmed here. If the two are different,
the received information is discarded and an error message is entered in
the diagnostic buffer (Event ID B130).
This check is not made if "PartnerNo" is = 0. Regardless of the sender,
each data frame addressed to the typical is passed on to the typical.
If "PartnerNo" is > 0 and this number is not found in the administration (in
DB-BasicData), an entry is made in the diagnostic buffer (event ID B101).
The CPU does not change to STOP. The block is then no longer
processed, however, until the error in the programming has been
corrected.
– If "PartnerNo = 0" is set, make sure that each partner sends the data
with a complete destination address (target subscriber no. and target
object no.).
– Use of the block in a node station
If the CPU of the node station maintains both connections to higher-
level subscribers as well as to lower-level stations, a data frame with
PartnerNo = 0 is transferred to all subscribers in the direction master
station and in the direction stations.
Object number of the partner
The number of the object (= DB number) on the partner with which the block
communicates.