EasyManuals Logo

Siemens TIM 1531 IRC User Manual

Siemens TIM 1531 IRC
338 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #151 background imageLoading...
Page #151 background image
Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
151
Explanation:
Image memory principle for spontaneous data transmission
•
TRUE
The data is transferred according to the image memory principle.
The image memory principle reduces the memory required for storing data
frames and produces as little data traffic on the WAN as possible. The
default TRUE is the correct choice in most cases.
•
FALSE
The data is transferred according to the send buffer principle.
The send buffer principle is only required with data points whose individual
data changes will be saved and transferred to the partner, for example
alarms with time stamps.
Conditional
Parameter:
Conditional
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
TRUE
Address
range:
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Using in typ
i-
cals
Bin04B_S, Ana04W_S, Cnt01D_S/Cnt04D_S, Set01W_R, Par12D_R,
Dat12D_S, Dat256D_S
Explanation:
Conditional spontaneous data transfer
You will information on this below with the parameter "Unconditional".
Unconditional
Parameter:
Unconditional
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Using in typ
i-
cals
Bin04B_S, Ana04W_S, Cnt01D_S/Cnt04D_S, Set01W_R, Par12D_R,
Dat12D_S, Dat256D_S