Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
161
Parameter:
TimeStamp
For the declaration, data type, range of values, default and function, refer to the section
Re-
occurring parameters (Page 144).
Typical
-
specific fun
c-
tions
With the setting TRUE the time stamp depends on the setting of the param
e-
ter "MeanValueGeneration":
•
MeanValueGeneration = FALSE
Instantaneous values are transferred in the data frame.
The time stamp in the data frame is identical to the time of acquisition of
the instantaneous values contained in the data frame.
•
MeanValueGeneration = TRUE
The data frame contains mean values.
The time stamp is identical to the time at which the mean value calculation
period was completed.
The start of the mean value calculation period is not included in the data
frame. This is, however, identical to the time stamp of the previously
transferred mean value frame.
Parameter:
ThresholdIntegration
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Explanation:
Threshold processing according to the integration principle
With this parameter, you can
specify whether the integration principle is used
in threshold value processing.
With the default FALSE the threshold value is calculated without integration. In
this case, you can expect less data traffic on the telecontrol line and locally
between CPU an
d TIM.
When MeanValueGeneration = TRUE, (analog values are sent as mean va
l-
ues), the "ThresholdIntegration" parameter has no meaning.
Parameter:
ZeroLimitation
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
TRUE
Explanati
on:
Zero limitation
If this parameter is activated negative values are be suppressed and replaced
with the value 0.