Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
162 Operating Instructions, 02/2018, C79000-G8976-C468-02
Parameter:
TriggerInput
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
Input
I 0.0
... I n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Explanation:
Trigger input
With the edge change 0
→ 1 of the "TriggerInput" input the transfer of the ana-
log value frame can be triggered at a required time.
Example:
T
ime-driven analog value transfer with time stamp for supplying an analog
value archive in the control center.
Make sure that you set the "ImageMemory" parameter to FALSE to prevent
these data frames with time stamps from being overwritten when saving on
th
e station TIM.
If the block calculates mean values, the duration of the calculation period is
decided by the "TriggerInput" input. The current period is ended and a new
period begun each time a transmission is triggered by this input. The interval
between
triggering a data frame twice determines the duration of the mean
value calculation period.
The FC Trigger block can be used for time
-driven triggering of a transmission
over "TriggerInput".
If you do not require the parameter, simply leave it open. The tr
ansfer should
then be triggered based on the "ThresholdValue" and "ThresholdIntegration"
threshold parameters.
"TriggerInput" actually only triggers transmission indirectly. With a 0
→ 1 edge
change at "TriggerInput", the data frame is put together with its current va
l-
ues/mean values and transferred to the local TIM. The TIM is responsible for
the actual transmission to the partner. With dedicated lines or wireless ne
t-
works the transfe
r is immediate. With a dial-up connection, it is possible that
the data frame is saved first on the TIM and sent at a later point in time. The
reason can, for example, be that the data frame is marked as "Conditional
spontaneous", see parameter "Conditional".
Parameter:
MeanValueGeneration
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE