Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
205
Explanation:
Return message from partner object: Object is set to local operation.
At the partner object that receives the parameter
s a local setpoint entry can
also be made.. The partner object Par12D_R must then be set to ’local’ at the
"Local" input parameter. The current status of the "Local" input parameter is
reported by the partner object and indicated here at the "LocalOperatio
n" out-
put.
After startup of the local or partner CPU, or after restoring a connection, an
automatic general request ensures that the local currently valid status is di
s-
played at "LocalOperation".
Parameter:
NewData
Explanation:
For the declaration, dat
a type, range of values, default and function, refer to
the section
Reoccurring parameters (Page 144).
Whenever the block has received new data an
d has output it to the outputs
"ReturnedSetpoint" or "LocalOperation", the "NewData" output is set to TRUE
for one OB1 cycle.
Parameter:
Release
Declaration:
IN_OUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
Memory bit
M 0.0 ... M n.7
Data bit
DBm.DBX 0.0 ... n.7
This is an in/out parameter (declaration IN_OUT). It is difficult to specify local
bit memory with this parameter type and this should not be used.