Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
206 Operating Instructions, 02/2018, C79000-G8976-C468-02
Trigger input for sending the currently p
ending parameter values
You can use this input parameter when the parameter is entered by software,
for example at an operator panel (OP). "Release" should then be set using a
function key on the OP. You can then enter several parameters initially on the
O
P. The parameters are transferred only when the Release function key is
A change check is performed only with signal 1 at the Release input. The data
double words from the data area configured with "ParameterInput" that have
changed since the la
st transfer are transferred.
If you always want to transfer the entire data area specified with "Paramete
r-
Input" and not only the changed parameter values, you should use the "R
e-
transmitAll" input parameter instead of "Release".
The "Release" input is rese
t automatically. You should therefore only specify
memory or data inputs as the input. The automatic reset would not work with a
digital input.
Data checks: The same safety checks are carried out as with ContinuousE
n-
If you do not require the parameter, simply leave it open.
This is an in/out parameter
(declaration IN_OUT). It is difficult to specify local
bit memory with this parameter type and this should not be used.