Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
207
Explanation:
Trigger input for retransferring the entire data area specified by "ParameterI
n-
put".
You can use this input parameter when
the parameter is entered by software,
for example at an operator panel (OP). "RetransmitAll" should then be set
using a function key on the OP. When a 1 signal is detected at the "Retran
s-
mitAll" input, the entire data area specified by "ParameterInput" is
transferred.
A change check is not performed
The "RetransmitAll" input is reset automatically. You should therefore only
specify memory or data inputs as the input. The automatic reset would not
work with a digital input. Since there is no change check, t
his would lead to
continuous transfer of all parameter values as long as the input has a 1 signal.
"RetransmitAll" can also be used as an option in addition to "Release" or
"ContinuousEnterFunct" when new parameter values were entered but could
not be tran
sferred to the partner (disrupted connection or the partner object is
set to ’local’). In this case you can then trigger repeated transfer of the entire
data area specified by "ParameterInput" using "RetransmitAll". All changes
that were previously entered
but are not yet available at the partner are con-
sistently included.
"RetransmitAll" can also be used as an independent transfer trigger when you
always want to send all entries and not just those that have changed. In this
case you can use "RetransmitAll"
instead of "Release" that only sends the
changed parameter values.
Data checks: The same safety checks are carried out as with "ContinuousE
n-
terFunct", see above.
If you do not require the parameter, simply leave it open.
Parameter:
ApplyRemoteParamMan
Declaration:
IN_OUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
This is an in/out parameter (declaration IN_OUT). It is difficult to specify local
bit memory with this parameter type and this should not be used.
Explan
ation:
Trigger input for synchronization of the input area with the returned area.
The input triggers a one
-
time synchronization of the ParameterInput input area
with the "ReturnedParameter" mirror back area. All the parameter values from
the "ReturnedPara
meter" mirror back area are then copied to the "Parameter-
Input" input area.
The send mailbox of the communications DB is also synchronized with the
returned parameter values.
"ApplyRemoteParamMan" is reset automatically. You should therefore only
specify m
emory or data inputs as the input. The automatic reset would not
work with a digital input. The result would be a constant synchronization as
long as the parameter has a 1 signal.
If you do not require the parameter, simply leave it open.