Configuration
4.8 Parameters of WAN networks
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
65
Access method
Access method
If required, set the default access method for the respective WAN type here:
Dedicated line: Polling / Polling with time slots
Dial-up network: ST7 protocol (spontaneous)
Frame parameters
Frame format
FT1.2
FT2
Acknowledgment type
Short acknowledgment (1 byte)
Long acknowledgment (5 bytes)
Repetition factor
The repetition factor decides how often a data frame that has not been acknowledged
positively is repeated.
Max. frame length
The maximum frame length depends on the largest length (240 bytes) of an ST7 data
frame within the network.
From this parameter time values (e.g. send repetition time) are derived for monitoring
functions.
Network settings
Dependence on direction
Direction dependency of the network
Duplex
Half duplex
Transmission speed
Speed at which the CP and modem communicate.